flag_canada.gif (18514 octets)

 

aqua_pulse.gif (990 octets) Septage Treatment Plant

 

Since July 1992, we have been operating an SBR type system supplied by ECO PROCESS & EQUIPMENT inc. This system has performed very well.

In fact, the SBR has been treating the following loads:

AVERAGE VALUES

Influent Effluent Performance
Flow
m3/d
BOD5
kg/d mg/L
SS
kg/d mg/L
Pt
kg/d mg/L
BOD5
kg/d mg/L
SS
kg/d mg/L
Pt
kg/d mg/L
BOD5
%
SS
%
Pt
%
70 133 1900 259 3700 2,6 36,6 2,03 29 2,24 32 0,27 3,8 98 99 90

The system we have been operating in St-Anaclet has given us performance results superior to 95% removal which is satisfactory.


Andre Marsan, ing.


Testimonies home